平高集团英文网站-pg电子游戏

平高集团英文网站-pg电子游戏
lw55-363 dead tank type sf6 circuit breaker

main product features:

1. the interrupter of the circuit breaker has a single break design and a simple and reasonable structure with high technology. it meets the requirements of iec 62271-1 and iec 62271-100.

2. strong breaking ability, long contact life (rated number of short-circuit breaking is up to 20 times) and long maintenance period.

3. except for the bushing unit which is packaged separately, the interrupter unit, hydraulic operation mechanism, current transformer and other components of the whole-pole circuit breaker are packaged as a whole unit, which does not require on-site docking and adjustment and is convenient for installation.

no.

item

unit

data

1

rated voltage

kv

363

2

rated current

a

5000

3

rated frequency

hz

50/60

4

rated short-time withstand current / time

ka/s

63/3

5

rated peak withstand current

ka

160

6

rated short-duration power-frequency withstand voltage

phase-to-earth

kv

510

across isolating distance

kv

510 210

rated lightning impulse withstand voltage

phase-to-earth

kv

1175

across isolating distance

kv

1175 295

rated switching impulse withstand voltage

phase-to-earth

kv

950

across isolating distance

kv

850 295

网站地图