平高集团英文网站-pg电子游戏

平高集团英文网站-pg电子游戏
lw55-550 dead tank sf6 circuit breaker

main product features:

1. the interrupter of the circuit breaker has a single break design and a simple and reasonable structure with high technology. it meets the requirements of iec 62271-1 and iec 62271-100.

2. strong breaking ability, long contact life (rated number of short-circuit breaking is up to 20 times) and long maintenance period.

3. except for bushing unit which is packaged separately, the interrupter unit, hydraulic operation mechanism, current transformer and other components of the whole-pole circuit breaker are packaged as a whole unit, which does not require on-site docking and adjustment and is convenient for installation.

4. the circuit breaker unit can be directly filled with sf6 gas without opening the interrupter during site installation, thus avoiding the invasion of dust and foreign matters.

main technical parameters:

no.

item

unit

data

1

rated voltage

kv

550

2

rated current

a

4000

3

rated frequency

hz

50/60

4

/ time

ka/s

50/3

5

rated peak withstand current

ka

125

6

rated short-duration power-frequency withstand voltage

phase-to-earth

kv

740

across isolating distance

kv

740315

rated lightning impulse withstand voltage

phase-to-earth

kv

1675

across isolating distance

kv

1675 450

rated switching impulse withstand voltage

phase-to-earth

kv

1300

across isolating distance

kv

1175 450

网站地图